Project WAVE
SEWA Operations Console

Water Quality & LIMS

Cross-validation of continuous analyzers vs LIMS grab samples · WHO/GCC-standard compliance

GCC-STD 149 · IN COMPLIANCE
Lab Drift Diagnostic Warning — Analyzer CL-KFRRO-04
Field chlorine reads 0.61 mg/L vs LIMS grab sample 0.72 mg/L (Δ +18%). Calibration drift beyond ISO-15839 tolerance.

Free Chlorine · Field Analyzer vs LIMS Grab · KFRRO (Khorfakkan)

Turbidity · Continuous vs LIMS · RHMRO (Sharjah)

LIMS Sample Registry — Last 24h

Sample IDSiteFree Cl (mg/L)Turb (NTU)pHField ΔResult
LIMS-2026-08411KFRRO0.720.147.4+18%DRIFT
LIMS-2026-08410ZBRPS0.610.097.6+2%OK
LIMS-2026-08409HMYRO0.680.117.5-3%OK
LIMS-2026-08408BDAPS0.740.087.6+1%OK
LIMS-2026-08407KLBDS0.650.167.4+4%OK